Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM06493
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/30/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/29/2006 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
06/29/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
06/27/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) RECEPTACLES NEED TO MEET REQUIREMENTS OF NEC 210.7 (C) 2) MAKE PANELS DIRECTORYS CLEAR AND LEGIABLE NEC 408.4 3) OK TO COMPLY |
|
06/26/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) EMERGENCY LIGHTING NEEDS TO BE PER PLAN AND WORKING PROPERLY 2) NEED BUSHING #4 AND LARGER WIRE 3) PROVIDE EARTHC GROUND FOR ALARM PANEL 4) PARTIAL INSPECTION ONLY-WORK IN PROGRESS NEC 210.7 |