Permit: T05CM06482

Parcel: 110055580

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T05CM06482

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/16/2006 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
TERMINATE SECONDARY DRAINS AS DISCUSSED WITH CHRIS
OK FOR CEILING TILES - LEAVE OUT AROUND EACH FAN COIL
02/06/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) I.D. PERM NUMBERS ON FAN COILS AND MATCHING SPLIT SYSTEM HEAT PUMPS
2) CLEAR UP ACCESS IN FRONT TO ALL FAN COILS. THIS IS GETTING TO BE A HABIT, NO RESPONSIBILITY TO MAINTAIN ACCESS FOR SERVICE
3) LEAVE ACCESS PANELS CLEAR OF ELECTRIC CONDUITS, CONDENSATE PIPING, PRIMARY AND SECONDARY