Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T05CM06482
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/16/2006 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* TERMINATE SECONDARY DRAINS AS DISCUSSED WITH CHRIS OK FOR CEILING TILES - LEAVE OUT AROUND EACH FAN COIL |
|
| 02/06/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) I.D. PERM NUMBERS ON FAN COILS AND MATCHING SPLIT SYSTEM HEAT PUMPS 2) CLEAR UP ACCESS IN FRONT TO ALL FAN COILS. THIS IS GETTING TO BE A HABIT, NO RESPONSIBILITY TO MAINTAIN ACCESS FOR SERVICE 3) LEAVE ACCESS PANELS CLEAR OF ELECTRIC CONDUITS, CONDENSATE PIPING, PRIMARY AND SECONDARY |