Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM06482
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/27/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOND TO BE AS PER 250.24 2. REJECTION PINS FOR FUSES NEEDED 3. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN GUTTER DUE TO BEING ENERGIZED. 4. LABEL PANEL COVER ON OUTSIDE OF COVER 5. TIGHTEN LOOSE TERMINALS & CONNECTIONS. 6. PLEASE COLOR CONDUCTORS FOR IDENTIFICATION AND CORRECTLY PLACE ON COORDINATED PHASES 7. SEPERATE GROUNDING & GROUNDED CONDUCTORS AT SUB PANEL. 8. A BOND WILL BE NEEDED AND ADDRESS TO PERMIT. |