Permit: T05CM06482

Parcel: 110055580

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM06482

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/31/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/27/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOND TO BE AS PER 250.24
2. REJECTION PINS FOR FUSES NEEDED
3. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN GUTTER DUE TO BEING ENERGIZED.
4. LABEL PANEL COVER ON OUTSIDE OF COVER
5. TIGHTEN LOOSE TERMINALS & CONNECTIONS.
6. PLEASE COLOR CONDUCTORS FOR IDENTIFICATION AND CORRECTLY PLACE ON COORDINATED PHASES
7. SEPERATE GROUNDING & GROUNDED CONDUCTORS AT SUB PANEL.
8. A BOND WILL BE NEEDED AND ADDRESS TO PERMIT.