Permit: T05CM06481

Parcel: 110055580

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM06481

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
03/31/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
03/10/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. SUPPORT VDV CABLING AS PER 725.6 - STERO-6' INTERVALS
2. FILL UNUSED OPENINGS IN JUNCTION BOXES - NOT EMPTY FITTINGS.
3. MANUFACTURERS FIXTURE CLIPS TO BE EFFECTIVE
4. SUPPORT M/C CABLES WITHIN 12" OF BOX AND 6'
5. SUPPORT FEEDER CONDUIT AS PER CODE 358.30
6. VERIFY BOX FILL
7. JUNCTION BOX TO BE GROUNDED 250.148
8. IDENTIFY GROUNDING CONDUCTOR AT LUG IN JUNCTION BOX
9. TIGHTEN LOOSE FITTINGS
10. MISSING EXIT SIGNS.
02/08/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*OK ROOMS 11-14,16,17,19-21
FINISH PREVIOUS ITEMS PATIENT AREAS
PLEASE REVISE PLANS AND LOAD CALLS FRO ADD RECEPTACLE
PLEASE PROVIDE A LETTER AUTHORIZING USE OF ENT CONFUIT ( PVC)
02/06/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*SECRULY SUPPORT M/C CABLES ALSO WITH IN 12"
SUPPORT VDV CABLE PER 725.6 & 800.6 DOWN WALLS
WHERE IS ACCESSIBILITY TO A/C DISCONNECT MEAN IN OTHER SUITE
SUPORT M/C CABLE AS PER 300.11 ALSO ??? DOUBLE
WIRING IN PATIENT AREAS TO BE AS PER 517.13( A) OR (B)