Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2006 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* OK COMPLETE BACKFILLING, USE CLEAN FILL TO 6" ABOVE TUBING BEFORE COMPLETING BACKFILL WITH MACHINERY AND EXISTING SOIL. |
|
| 03/21/2006 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* A PRESSURE TEST IS REQUIRED TO CHECK FOR LEAKS BEFORE APPROVAL TO COVER |
|
| 03/16/2006 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WATER LINE NOT UNDER TEST 2. INSTALLATION IS IN VIOLATION OF THE UNIFORM PLUMBING CODE AND THE MANUFACTURERS INSTALLATION REQUIREMENTS. SEE UPC 314.3 "PIPING IN GROUND SHALL BE LAID ON A FIRM BED FOR ITS ENTIRE LENGTH" UPC SEC 315.4 "PIPING SHALL BE BACKFILLED TO 12" ABOVE TOP OF PIPE WITH CLEAN EARTH, THAT DOES NOT CONTAIN ROCKS OR DEBRIS." PROVIDE CLEAN FILL AT LOCATION PRIOR TO INSPECTION SO THAT I CAN BE SURE THAT THE ROCKY, CHUNKY FILL THAT IS PRESENT WILL NOT BE USED. VANGUARD STANDARDS REQUIRE BEDDING AND HAUNCHING OF PIPING. |
|
| 01/20/2006 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* |