Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T05CM06469

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/04/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
03/31/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
FILL TUB TO FLOOD LEVEL
SECURE WATER LINES AT TUB AND AT REAR HB
CALL FOR HCS AND ROUGH INSPECTIONS ALSO.
03/28/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEE NOTES FROM PREVIOUS INSPECTION.
2. FILL TUB & SHOWER TO FLOOD LEVEL.
03/22/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
WATER LINES TOUCHING FHA STRAPS AND BANG PLATES
PLAN CALLS FOR 3/4" TO REAR HOSE BIB DO YOU HAVE A REVISION FOR 1/2".
TRAP ARM FOR LAVATORY IN REAR BATHROOM IS 46"
UPC ALLOWS 42" MAXIMUM FOR A 1 1/2 TRAP ARM.
USE OF AAV AT KIT SINK REQUIRES PLAN REVISION
THERE IS A LOT OF WATER ON FLOOR IS YOUR TEST HOLDING?