Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM06461
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/05/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/04/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
04/25/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* SYSTEM IS NOT HOLDING A WATER TEST. 9:15 AM THERE IS NO WATER IN DWV THERE IS NO VISIBLE WETNESS IN BUILDING, BUT THERE MAY BE A SIGNIFICANT LEAK UNDER THE BUILDING OR MAYBE ITS OUTSIDE OF THE BUILDING. IT IS YOUR JOB TO CORRECT THIS AND PROVIDE A TEST. THIS IS THE FOURTH TIME THAT I HAVE DONE THIS INSPECTION. A REFEE IS BEING ASSESSED AND MUST BE PAID WITHIN 5 DAYS OR NO MORE INSPECTIONS WILL BE PERFORMED. ALSO PLAN SHOWS GAS TO DRYER, GAS PIPING DOES NOT GO TO DRYER LOCATION, PROVIDE REVISED PLAN. |
|
04/24/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* DWV NOT UNDER TEST SUPPORT HORIZONTAL GAS PIPING BRANCH TO FURNACE. |
|
04/21/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOT UNDER TEST SECURE ICE MAKER BOX |
|
04/19/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |