Permit: T05CM06455

Parcel: 10821018U

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T05CM06455

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/13/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/10/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CONDUCTORS #4 AND LARGER NEED BUSHING NEC. 300.4 (F)
2. I NEED ALL SERVICE EQUIPMENT OPEN FOR INSPECTION INCLUDING TERMINATION CAN.
3. USE SINGLE CONDUCTORS UNLESS LUGS ARE LISTED FOR MULTIPLE CONDUCTORS.
03/09/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN FRONT AREA SOFFITS AND BATH AREA HARD LIDS ALSO, OFFICE/BATH AREA HARD LIDS.
*NOTE* SECURE/SUPPORT LOW VOLTAGE WIRING IN A NEAT AND WORKMAN LIKE MANNER AS NEEDED NEC 800.6
03/02/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN WALLS
*NOTE: TALKED WITH FERNANDO, ASKED HIM TO CHECK WITH BUILDING INSPECTOR CONCERNING BOX PLACEMENT IN RATED WALL BETWEEN UNITS. MAY OR MAY NOT BE A PROBLEM.
02/08/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*OK TO COVER PANEL FEEDERS UNDR SLAB
ORIGINAL PLAN WAS TO RUN FEEDERS OVERHEAD
PROVIDE LETTER FOR PLAN REVISION FROM ARCHITECT