Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM06455
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/13/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/10/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CONDUCTORS #4 AND LARGER NEED BUSHING NEC. 300.4 (F) 2. I NEED ALL SERVICE EQUIPMENT OPEN FOR INSPECTION INCLUDING TERMINATION CAN. 3. USE SINGLE CONDUCTORS UNLESS LUGS ARE LISTED FOR MULTIPLE CONDUCTORS. |
|
03/09/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN FRONT AREA SOFFITS AND BATH AREA HARD LIDS ALSO, OFFICE/BATH AREA HARD LIDS. *NOTE* SECURE/SUPPORT LOW VOLTAGE WIRING IN A NEAT AND WORKMAN LIKE MANNER AS NEEDED NEC 800.6 |
|
03/02/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN WALLS *NOTE: TALKED WITH FERNANDO, ASKED HIM TO CHECK WITH BUILDING INSPECTOR CONCERNING BOX PLACEMENT IN RATED WALL BETWEEN UNITS. MAY OR MAY NOT BE A PROBLEM. |
|
02/08/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*OK TO COVER PANEL FEEDERS UNDR SLAB ORIGINAL PLAN WAS TO RUN FEEDERS OVERHEAD PROVIDE LETTER FOR PLAN REVISION FROM ARCHITECT |