Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM06454
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/21/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1. CORRECTIONS MADE OK 2. OK TO COVER ALL AREAS |
|
04/20/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP. 2. HORIZONTAL VENTING BELOW THE FLOOD RIM RESTRICTED TO STRUCTURAL CONDITIONS AND ARE TO BE DRAINAGE FITTINGS. 3. TRAP FOR STANDPIPE RECEPTOR TO BE ROUGHED IN NO LESS THAN 6" AFF NOR MORE THAN 18" AFF STAND PIPE TO BE BETWEEN 18"-30" 4. ALL OVERHEAD PIPE TO BE SUPPORTED. 5. TRAP ARMS TO BE SUPPORTED AS CLOSE TO THE SWEEP AS POSSIBLE. PLUMBERS TAPE NOT AN APPROVED STRAPPING DO NOT SUPPORT FROM FITTING. |
|
03/23/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK TO COVER FIRE SEPARATION SUBJ TO TEST |