Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/15/2006 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 12/12/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DBL LUGGING OF GROUND WIRES OF DIFFERENT GAUGE NOT ALLOWED 2) DBL LUGGING OF NEUTRAL WIRES NOT ALLOWED 3) ACCESS TO A/C DISCONNECT BLOCKED BY CONDENSER-MUST HAVE 30" X 30" WORK AREA 4) A/C CONDENSER NOT STABLE ON PAD |