Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 07/20/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING SHEAR TRANSFER 2) MISSING NAILING THROUGHOUT |
|
| 07/19/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INCOMPLETE 2) STOPPED INSPECTION |
|
| 07/18/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO CHANGE FORM 7/17/06 |
|
| 07/17/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TRUSS A-1 NOT BRACED PER PLAN 2) 3-16D NAILS REQUIRED AT EACH BIRD BOARD TOE NAILED PER 7/D-1 3) DIAGONAL BRACES REQUIRE 2-16D NAILS AT EACH END 4) SHEARWALL EDGES MUST BE BLOCKED AND NAILED PER PLAN 5) GLUE LAM BEAM POST NOT CLIPPED WITH SAME UP LIFT AS EPCM HARDWARE 6) EPCM HARDWARE AND MST 27 STRAP MISSING THROUGHOUT 7) NO LADDER ACCESS TO ROOF 8) STOPPED INSPECTION |