Permit: T05CM06441

Parcel: 141091220


Addresses:

6613 E GEHRIG LN


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T05CM06441

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
12/11/2006 FRAMING Approved IVRS - Inspection :*
12/08/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FIRE STOP 2ND FLOOR PENETRATIONS (REPEAT)
2) MAX ALLOWED STAIR BULL NOSE 1 1/4 INCHES
3) NAIL PROTECT DRYER VENT
4) BEARING WALL BY STAIR BOTTOM PLATE NOT NAILED
5) HOLD DOWNS REQUIRED 16D NAILS
12/04/2006 FRAMING Not ready for Inspection IVRS - Inspection :*
1) NOT READY PER SUPER
11/29/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) VACUUM BREAKERS REQUIRED ON HOSE BIBS
2) STUCCO MESH INCOMPLETE
3) INSTALL AND SEAL SCUPPERS
4) FILL DWV
5) FIRESTOP HOLES THROUGH 2ND FLOOR
6) BEND STAPLES OVER BEHIND HOME RUNS
7) NEGATIVE SLOPE 2" DRAIN FROM WASHING MACHINE
8) HOLDOWN INSTALLATION INCOMPLETE
9) STOPPED INSPECTION