Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2007 | MECHANICAL - ABOVE CEILING | Approved | ||
| 08/30/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SUPPLY/RETURN DUCT SYSTEM ABOVE GRID IN FRONT ENTRANCE LOBBY, OK OK FOR CEILING TILES. |
|
| 08/04/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/19/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* CANNOT ACCEPT AS INSTALLED. THIS INSTALLATION DOES NOT MEET THE INTENT OF THE CODE. THIS NEEDS TO BE CORRECTED OR PROVIDE AN ALTERNATE METHOD OF INSTALLATION. |
|
| 06/30/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* IDENTIFY FAN COILS. PROVIDE FUSES IN DISCONNECTS PROVIDE SECONDARY DRAINS LEAVE OUT TILES AROUND FAN COILS CONDENSATE PUMP CANNOT HAVE A PLUG ABOVE CEILING CONNECT OVERFLOW SENSOR ON PUMP. FINISH ALL DUCT TO DIFFUSER CONNECTIONS. |