Permit: T05CM06438

Parcel: 12307259B


Addresses:

2127 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
01/23/2007 MECHANICAL - ABOVE CEILING Approved
08/30/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
SUPPLY/RETURN DUCT SYSTEM ABOVE GRID IN FRONT ENTRANCE LOBBY, OK
OK FOR CEILING TILES.
08/04/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/19/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
CANNOT ACCEPT AS INSTALLED.
THIS INSTALLATION DOES NOT MEET THE INTENT OF THE CODE. THIS NEEDS TO BE CORRECTED OR PROVIDE AN ALTERNATE METHOD OF INSTALLATION.
06/30/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
IDENTIFY FAN COILS.
PROVIDE FUSES IN DISCONNECTS
PROVIDE SECONDARY DRAINS
LEAVE OUT TILES AROUND FAN COILS
CONDENSATE PUMP CANNOT HAVE A PLUG ABOVE CEILING
CONNECT OVERFLOW SENSOR ON PUMP.
FINISH ALL DUCT TO DIFFUSER CONNECTIONS.