Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/26/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 01/23/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. STILL NO TEMPERATURE CONTROL DEVICE AT LAVATORIES. PAT - ARGUMENTATIVE AND ACCUSATORY |
|
| 01/23/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* COULD NOT LOCATE MIXING VALVE FOR TEMPERED WATER CONNECTIONS FOR SINK ARE CONNECTED TO 3/4 SUPPLY TO WH. CONNECT TO 1 1/4 PIPING. PAINT UNPROTECTED VENT FROM SINK. |
|
| 08/29/2006 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* - PLANS APPROVED UNDER 2003 UPC - PLEASE COMPLY W/SEC 414.1 REQUIRING AN ADDITIONAL TEMPERATURE CONTROL DEVICE FOR PUBLIC USE LAVITORIES |
|
| 08/04/2006 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* - WH REQUIRES DIELECTRIC FITTINGS AT TANK CONNECTION, SUPPORT OF CW PIPING AT EXP TANK, ALSO REMOVE EXCESS FLUX FROM SOLDER JOINTS W/A DAMP RAG PER UPC INSTALLATION STANDARDS AND COMPLETE INSULATION OF HOT & REC PIPING. - ALL SAFETY DEVICES ON WH ARE INSTALLED, ALL FIXTURES ON GROUND FLOOR ARE PROPERLY SET AND OPERATING. - NO SAFETY ISSUED PREVENTING TCO ARE APPARENT |
|
| 08/03/2006 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1ST FLOOR FIXTURES ARE SET, WH AND WH SAFETY FEATURES ARE INSTALLED BUT WATER IS OFF FIXTURES DO NOT REQUIRE WATER TO BE ON FOR FINAL INSPECTION. INTERMEDIATE INSPECTIONS NOT APPROVED |