Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM06400
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/28/2006 | FRAMING | Approved | IVRS - Inspection :* | |
07/17/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE TRUSS DRAWING TO CHECK F-3 TRUSS 2) GARAGE TRUSS LAYOUT IS NOT PER APPROVED PLAN. BUILD TO PLAN OR REVISE TO AS BUILT 3) STAIR LANDING IS NOT PER PLAN 4) STAIR PONY WALL MUST SUPPORT 200 POUND FORCE 5) HEADERS MUST BEARON ON TRIMMERS 6) SECOND FLOOR SHEAR WALLS NOT ANCHORED PER PLAN 7) BEARING STUDS AT KITCHEN SINK BORED MORE THAN 40 PERCENT. REPLACE OR ADD STUD SHOES |