Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM06399
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/28/2006 | FRAMING | Approved | IVRS - Inspection :* | |
06/26/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS 3 X 8 FROM 6/22/06 NOT DONE 2) EITHER INSTALL GAS LINES PER PLAN OR REMOVE FROM PLAN AND PERMIT |
|
06/22/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LATHE AND FLAME BARRIER MISSING AT VENTS 2) INSTALL SHEAR BLOCK AT ELECTRIC ? 3) SILL PLATES REQUIRE 2 ANCHOR BOLTS 4) RED HEAD ANCHORS LOOSE 5) BEARING WALL AT FURNACE NOT ANCHORED 6) CLIP AND ANCHOR BEARING POSTS 7) NO DWV WATER TEST 8) 3/DT1 NOT DONE AT SHEAR CHANNELS |