Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM06398
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/03/2006 | FRAMING | Approved | IVRS - Inspection :* NO FRAMING CHANGE FIX POSTS + FIRE BLOCK OK TO INSULATE |
|
06/30/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
06/29/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS 4, 5, 6 AND 7 FROM 6/23/06 NOT DONE |
|
06/23/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLANS CALL FOR GAS LINES. YOU MUST INSTALL ALL GAS LINES OR HAVE PLANS AND PERMIT DELETE ALL GAS LINES 2) HOUSE WAS FORMED WITH 3" X .131 10D NAILS WHERE 16D NAILS ARE REQUIRED. HAVE ENGINEER OF RECORD PROVIDE CITY OF TUCSON RECOMMENDATION AND REPAIR 3) SHIM HEADERS 4) FIRE STOP CHANNEL BY ENTRY 6050 5) DBL/TRIPPLE 2 X POSTS NOT NAILED PER CODE 6) EPCM MISSING LR GLB 7) NAIL PROTECT DWV AT PANTRY 8) STUCCO WEEP SCREED MUST EXTEND 2" BELOW FINISH FLOOR |