Permit: T05CM06398

Parcel: 141091080


Addresses:

6657 E WRIGLEY WY


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T05CM06398

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
07/03/2006 FRAMING Approved IVRS - Inspection :*
NO FRAMING CHANGE
FIX POSTS + FIRE BLOCK
OK TO INSULATE
06/30/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/29/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS 4, 5, 6 AND 7 FROM 6/23/06 NOT DONE
06/23/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLANS CALL FOR GAS LINES. YOU MUST INSTALL ALL GAS LINES OR HAVE PLANS AND PERMIT DELETE ALL GAS LINES
2) HOUSE WAS FORMED WITH 3" X .131 10D NAILS WHERE 16D NAILS ARE REQUIRED. HAVE ENGINEER OF RECORD PROVIDE CITY OF TUCSON RECOMMENDATION AND REPAIR
3) SHIM HEADERS
4) FIRE STOP CHANNEL BY ENTRY 6050
5) DBL/TRIPPLE 2 X POSTS NOT NAILED PER CODE
6) EPCM MISSING LR GLB
7) NAIL PROTECT DWV AT PANTRY
8) STUCCO WEEP SCREED MUST EXTEND 2" BELOW FINISH FLOOR