Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM06383
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/02/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/30/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* #912 -- HAS OPEN NEUTRAL ON KITCHEN RECEPT #909 -- ARC FAULT NOT WORKING POWER CHECK ALL UNITS PRIOR TO CALLING INSP. |
|
04/18/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* - OK GROUNDING AT SERVICE EQUIP. - POST BOND FOR TEMP POWER FOR TEST |
|
04/15/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. GROUNDING ELECTRODE CONDUCTOR CANNOT BE SPLICED OTHER THAN IRREVERSIBLE TYPE - PER 250 NEC 2. BOXES AT COUNTERTOPS NOT TO BE RECESSED MORE THAN 1/4" 3. INSTALL BOND BUSHING ON RISER CONDUITS PER 250 NEC 4. POST BOND FOR TEMP POWER FOR TEST |