Permit: T05CM06383

Parcel: 12907006U

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/02/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/30/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
#912 -- HAS OPEN NEUTRAL ON KITCHEN RECEPT
#909 -- ARC FAULT NOT WORKING

POWER CHECK ALL UNITS PRIOR TO CALLING INSP.
04/18/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
- OK GROUNDING AT SERVICE EQUIP.
- POST BOND FOR TEMP POWER FOR TEST
04/15/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. GROUNDING ELECTRODE CONDUCTOR CANNOT BE SPLICED OTHER THAN IRREVERSIBLE TYPE - PER 250 NEC
2. BOXES AT COUNTERTOPS NOT TO BE RECESSED MORE THAN 1/4"
3. INSTALL BOND BUSHING ON RISER CONDUITS PER 250 NEC
4. POST BOND FOR TEMP POWER FOR TEST