Permit: T05CM06377

Parcel: 141091060


Addresses:

6641 E WRIGLEY WY


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T05CM06377

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/31/2006 BUILDING - FINAL Approved IVRS - Inspection :*
08/30/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ADDRESS
2) DBL LUGGING OF WIRES OF DIFFERENT GAGE NOT ALLOWED
3) ACCESS TO A/C CONDENSOR DISCONNECT BLOCKED BY UNIT. MUST HAVE 30" X 30" UNOBSTRUCTED WORK AREA
4) PROVIDE CONDENSOR INSTALLATION MANUAL TO CHECK CLEARANCE
5) SECURE FLEX CONDUIT WITHIN 12" OF FAU