Permit: T05CM06356

Parcel: 13332013H


Addresses:

9462 E LANTERRA CT

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
06/26/2006 FRAMING Approved IVRS - Inspection :*
06/23/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REPLACE BROKEN FIRE BLOCK IN GARAGE
2) DOORBELL TRANSFORMER NOT MOVED
3) SWITCH AND RECEPTACLE LOOSE HALLWAY
4) NEED NOTES FROM SOIL INSPECTIONS
5) I BELIEVE A 3" CLEANOUT WAS NEEDED IN ONE OF THE BATHROOMS
6) PLEASE CORRECT ALL ITEMS FROM PRIOR INSPECTIONS BEFORE RECALLING
06/21/2006 FRAMING Partial Approval IVRS - Inspection :*
1) REPAIR FIRE BLOCK SOUTH WALL GARAGE
2) MESH ON HOUSE STAPLED OFF; PARAPETS AND CAULKING NOT COMPLETE
3) DOOR BELL TRANSFORMER CANNOT BE IN CLOSET
4) PEX NOT PERMITTED FOR T/P LINE
5) NO GAS TO KITCHEN ?
6) A/C REGISTER MASTER BEDROOM CROOKED
7) NEED PLOT PLAN CHANGE FOR FRONT PORCH PRIOR TO FINAL