Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM06346
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/21/2006 | ELECTRIC - INTERMEDIATE | Approved | PER EL FINAL | |
06/26/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED CITY APPROVED REVISED PLAN FOR INSPECTION AND ALL OTHER PREVIOUS CORRECTIONS |
|
01/20/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* * ALL WIRING TO COMPLY WITH NATIONAL ELEC. CODE * RESEARCH & MULTI-PURPOSE ROOMS ARE CONSIDERED AS "PLACE OF ASSEMBLY" AND MUST COMPLY WITH ART. 518 NEC * ALL FIXTURES, CONDUITS, J-BOXES, ETC. MUST BE SECURED AND PROPERLY SUPPORTED AS REQUIRED BY THE N.E.C AND THE INTERNATIONAL BUILDING CODE *NOTE-THE FLOOR PLAN FOR THE T.I HAS BEEN REDLINED (BY MYSELF) INDICATING SWITCHES, RECEPTACLES, J-BOXES, LIGHTS, FANS, ETC. THAT HAVE NEVER BEEN INSPECTED BY THE CITY OF TUCSON. YOU WILL NEED TO SECURE THE SERVICES OF A L-11 OR K-11 LIC. ELECTRICAL CONTRACTOR TO REVIEW THE EXISTING CONDITIONS AND TO CORRECT ANY & ALL DEFICIENCIES PRIOR TO MY INSPECTION. *ALL REPAIRS, CIRCUITING, SWITCHES, RECEPTACLES, LIGHTING, FANS AND JUNCTION BOXES MUST COINCIDE WITH THE ARCH. - ENGINEERS CITY APPROVED PLANS (PLANS WILL BE SUBJECT TO APPROVAL BY THE CITY OF TUCSON ELECTRICAL PLANS EXAMINER. A COMPLETE ACCURATE CODE COMPLYING SET OF PLANS WILL BE REQUIRED INCLUDING LOAD CALCULATIONS, ETC. ANY QUESTIONS I CAN BE REACHED AT 954-0161 BOB SUBA |
|
01/06/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*NOTE: CEILING HAS EXTENSION CORDS ( EXTENSION CORD WIRING CANNOT BE USED IN LIEU OF A PERMANENT APPROVED WIRING METHOD) THE SCHOOL IS CONSIDERED A PLACE OR ASSEMBLY AND N.M CABLE ( ROMEX) IS NOT AN ACCEPTED WIRING METHODS THIS NEEDS TO BE BROUGHT UP TO THE MIN. STANDARD OF THE NATIONAL ELEC. CODE. ALSO ALL WALLS WHICH ARE NOT REFLECTED ON THE LAST APPROVED PLAN WITH THE CITY OF TUCSON AS REFLECTED THROUGH THE CERTIFICATE OF OCCUPANCY WILL NEED TO BE OPENED UP FOR INSPECTION PURPOSES ( SPECIFICALLY THE ELECTRICAL) |
|
01/05/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*EAST PHASE OK |