Permit: T05CM06336

Parcel: 124082260


Addresses:

1304 E 10TH ST #01


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T05CM06336

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/15/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
PLANS CALL FOR 200A FEEDERS
PRIOR TO FINAL PROVIDE APPROVAL FROM OWNER OR GENERAL ON CHANGES TO FEEDERS, IF REPLACED TO 200A STATUS -- RECALL INSPECTION.
11/13/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
11/08/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) HAVE OVER FILLED ENTRY LIGHT BOXES AT EXTERIOR, REFER, 2 GANG TOP OF STAIRS-CHECK ALL J-BOXES
2) IDENTIFY WHITE USED AS HOT
3) NAILS NOT ALLOWED THROUGH DEVICE BOXES (OR SCREWS)
4) SMOKE DETECTORS TO BE MINIMUM 36" FROM SUPPLY/RETURN DUCTS
5) ADD NAIL PLATES AS NEEDED
6) REMOVE BOND STRAPS IN SUB-PANELS
7) GROUND ALL METAL BOXES AND SEAL UNUSED OPENINGS
8) FEEDER TO SUB PANEL UNDERSIZED
9) HAVE NICKS IN CONDUCTORS
10) PANEL TO BE OUTSIDE OF BATHROOM
11) SECURE/STRAP FEEDERS THROUGHOUT
12) SECURE ROMEX IN SOFFIT AREAS