Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM06336
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/15/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* PLANS CALL FOR 200A FEEDERS PRIOR TO FINAL PROVIDE APPROVAL FROM OWNER OR GENERAL ON CHANGES TO FEEDERS, IF REPLACED TO 200A STATUS -- RECALL INSPECTION. |
|
11/13/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
11/08/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) HAVE OVER FILLED ENTRY LIGHT BOXES AT EXTERIOR, REFER, 2 GANG TOP OF STAIRS-CHECK ALL J-BOXES 2) IDENTIFY WHITE USED AS HOT 3) NAILS NOT ALLOWED THROUGH DEVICE BOXES (OR SCREWS) 4) SMOKE DETECTORS TO BE MINIMUM 36" FROM SUPPLY/RETURN DUCTS 5) ADD NAIL PLATES AS NEEDED 6) REMOVE BOND STRAPS IN SUB-PANELS 7) GROUND ALL METAL BOXES AND SEAL UNUSED OPENINGS 8) FEEDER TO SUB PANEL UNDERSIZED 9) HAVE NICKS IN CONDUCTORS 10) PANEL TO BE OUTSIDE OF BATHROOM 11) SECURE/STRAP FEEDERS THROUGHOUT 12) SECURE ROMEX IN SOFFIT AREAS |