Permit: T05CM06332

Parcel: 119410180


Addresses:

1937 W AJO WY


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T05CM06332

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/21/2006 BUILDING - FINAL Approved IVRS - Inspection :*
07/19/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DRAIN THROUGH BACK WALL
2) ANTI-TIP ON RANGE
3) EXTERIOR LIGHTS
07/17/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXTERIOR FIXTURES REQUIRED TO BE FULL CUT-OFF
2) SET SCREW AT HOSE BIB MUST BE TIGHTENED UNTIL IT SHEARS OFF
3) CLAMP WHIP TO A/C UNIT 12" FROM DISCONNECT
4) EXTERIOR GRADE MUST SLOPE AWAY FROM HOUSE MINIMUM 6"
5) CLEAN DEBRIS OUT OF HOUSE
6) SEAL CEILING AT FURNACE
7) CHECK ANTI-TIP ON RANGE