Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/12/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* NO WORK PROGRESS |
|
| 04/11/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TEMP C OF O SUBJECT TO BUILDING INSPECTOR. 1. WILL NEED CITY STAMPED REVISIONS FOR FINAL. |
|
| 04/10/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* WAITING ON NRTL REP TO TEST EQUIPMENT PLEASE CONTACT ME AT 909-4749 RICK |
|
| 04/06/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* PAPER WORK SUPPLIED IS NOT A FIELD EVALUATION REPORT OR LABELING AS SUCH. PLEASE CONTACT APPROPRIATE NRTL FOR TESTING OF ASSEMBLY. |
|
| 03/31/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 03/28/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. X-RAY EQUIPMENT NEEDS AN ASSEMBLY LISTING. 2. SUPPORT M/C CABLE AS PER CODES 12" & 6' 3. FINISH WALL WORK 4. PNAEL MORE THAN 1/4" FROM CAN TO SURFACE 5. FINISH INSTALLING COVERS ON WALL DUCTS 6. NEED CITY STAMP ON REVISIONS 7. CONDUCTORS AT 100A X-RAY DISCONNECT NOT AS PER PLANS. 8. NEED GROUNDING EQUIPMENT CONDUCTOR AT X-RAY DISCONNECT. |
|
| 03/24/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |