Inspection History Details
Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/12/2006 | SHEET ROCK NAILING | Approved | IVRS - Inspection :* | |
| 06/09/2006 | SHEET ROCK NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GARAGE CEILING UNDER OCCUPIED SPACE MUST BE FASTENED AT 6" O.C MAXIMUM. 2. LIVING ROOM #1 SHEAR WALL MUST BE NAILED AT TOP PLATE AT 7" OK 3. MBR SHEAR WALLS NAILED IN EXCESS OF 7" OC AND NAILS CANNOT BE WITHIN 3/8" OF EDGES. 4. BR-2 #-3 SHEAR NOT NAILED. 5. M. TOILET TOP PLATE NOT NAILED. |
|
| 06/08/2006 | SHEET ROCK NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED VERIFICATION OF 1025 COMPLETE APPROVAL 2) STOPPED INSPECTION |