Permit: T05CM06310

Parcel: 140550600

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
05/03/2006 FRAMING Approved IVRS - Inspection :*
04/26/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HANGER ON DIAGONAL 3 1/8" X 12 GLB REQUIRED AT LIVING ROOM HAVE ENGINEER SPECIFY
2) GARAGE SHEARWALL PAHD 2 NOT INSTALLED
04/24/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HANGER AT ROOF GIRDER, BEAMS ROOF HU 410-2900 POUNDS SOUTH & HGU5 26/2 = 4800 NORTH, HANGERS INSTALLED ARE UNDER SIZED
2) LEAK IN 3" ABS GARAGE LID
3) A.B. AT SHEARWALL #7 AT STAIRS 24" ON CENTER 1/2" DIAMETER
4) ALL TRUSSES TO GIRDER & BEAM, UST THA 29 TYP
5) DINING ROOM #6 SHEAR A.B.'S AT 16" ON CENTER
6) BLOCK ALL MECH DUCTS