Permit: T05CM06310

Parcel: 140550600

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
04/10/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
04/04/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEM 5, 6 AND 7 FROM PRIOR INSPECTION
2) GLU LAM BEARING AND HANGER NOT PER PLAN
3) OK TO DRY IN
03/30/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLY WITH PREVIOUS NOTES 5, 6 AND 8
2) RETRO FIT REQUIRED AT ENTRY DOOR
3) COMPLY WITH DETAIL DT2 BLOCKING
03/20/2006 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
03/06/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STRAP NON OVER LAPPING DBL TOP PLATES 2ND FLOOR
2) PROVIDE ENGINEER DETAIL OF 4 X 6 POST CONNECTION TO PLATE
3) CS STRAPS MUST BE 48" LONG AND CONNECT TO STUDS
4) SHEAR WALL 6 NOT NAILED AT 4" + 12"
5) HOLDOWN MISSING ENTRY
6) TRUSSES TJI NOT PER 3/DT2
7) ROOF NAIL OK PENDING PLAN REVISION OF 6/DT2 AND 3/DT2 TO AS BUILT
8) GARAGE CORNERS REQUIRE 4 X 6 POSTS WITH ? CAPS
9) S.W. CORNER 2ND FLOOR NOT SUPPORTED
10) CS STRAPS REQUIRED AT 48"ON CENTER