Permit: T05CM06308

Parcel: 140550610

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
05/18/2006 FRAMING Approved IVRS - Inspection :*
05/15/2006 FRAMING Not ready for Inspection IVRS - Inspection :*
1) NOT READY PER SUPER
05/11/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS 1, 2, 6, 8, 10 & 11 FROM 5/9/06 NOT DONE
05/09/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 2 X TRUSS BLOCKING AT GARAGE 8/DT2
2) DWV LEAK
3) FLOOR TRUSS HANGERS MISSING NAILS
4) SEAL SECOND FLOOR PENETRATIONS
5) NAIL 2 X 12 LEDGER TO BEAM
6) LIVING ROOM INSTERIOR BEARING WALL MISSING ANCHOR BOLTS 6'
7) MINIMUM STAIR WIDTH 36" NOT PER CODE
8) NAIL 2ND FLOOR SHEAR WALL BOTTOM PLATES PER PLAN
9) BLOCK DUCT BOOTS
10) MAKE UP AIR INTAKE MUST BE 10FT FROM SEWER VENT
11) 4 X 4 AND 4 X 6 POSTS MISSING EITHER SIDE OF STAIRS
05/08/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO DWV TEST
2) FIRE BLOCK CHASES THROUGHOUT
3) DUCT NOT SUPPORTED ON 3 SIDES
4) DRYER VENT DAMAGED