Permit: T05CM06242

Parcel: 132164380


Addresses:

4761 S WARREN AV


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T05CM06242

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
06/06/2007 FRAMING Approved IVRS - Inspection :*
05/15/2007 FRAMING Partial Approval IVRS - Inspection :*
11/13/2006 FRAMING Partial Approval IVRS - Inspection :*
09/08/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BEAM ON PORCH SUPPOSED TO BE 6 X 8
2) SEE BELOW OK TO CONTINUE
3) WANT TO SEE ELECTRICAL BOX ONCE INTERIOR WALLS HAVE BEEN REMOVED AND REST OF FRAMING
4) OK TO INSULATE OUTSIDE WALLS
07/21/2006 FRAMING Partial Approval IVRS - Inspection :*
1) APPROVED TO LATHE
2) COMPLETE ALL INTERMEDIATES
06/23/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CHECK ROOF FRAMING PLAN FOR REQUIRED JOIST AND BEAM SIZES
2) COMPLETE ALL ELECTRICAL PRIOR TO FRAME INSPECTION
3) ROMEX CONNECTOR REQUIRED AT ALL METAL BOXES
4) SLEEVE WIRE THRU CMU WALLS
5) REVISE PLAN TO REFLECT FRONT ADDITION EXTENSION