Permit: T05CM06235

Parcel: 118101580


Addresses:

2280 S DEVON LP


Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Permit Number - T05CM06235

Inspection Description - REINFORCED MASONRY PRE-GROUT

Inspection Status - Approved

Date Description Inspector Results Comments
05/18/2007 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
05/11/2007 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLY WITH PRIOR INSPECTION REQUEST
05/10/2007 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CORNERS HAVE FRESH GROUT UP TO 6'-INSPECTION NOT POSSIBLE FOR LOWER REBAR-PROVIDE PACHO METER TEST
2) TIE BOND BEAM REBAR TO EXISTING WALLS OR PROVIDE APPROVED ALTERNATE
05/08/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) NEED #5 VERTICAL AT CORNERS. CONTRACTOR SAY'S THEY ARE ON THE WAY. GAVE OK TO GROUT AT OWN RISK. IF NEXT INSPECTOR DOES NOT SEE #5 VERTS AT CORNERS-WILL HAVE TO REMOVE AND START OVER