Permit: T05CM06213

Parcel: 141092270

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T05CM06213

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
06/02/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
05/30/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 3 PT BEARING TRUSSES NOT BEARING AT MID POINT
2) TRUSS BRACING MISSING TRUSSES C02BV
3) #9 SHEARWALLS REQUIRE NAILING AT 3" ON CENTER AT EDGES
4) SHEARWALL CHANNELS NOT NAILED PER 5/SD2
5) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF PLATE SURFACES-USE FHA STRAPS
6) #8 SHEARWALLS REQUIRE EDGE NAILING AT 4" ON CENTER AND STUDS WITH HOLDOWNS REQUIRE NAILING
7) DIAGONAL WIND BRACES REQUIRE 2-16D NAILS AT ENDS
8) 8/SD3 NOT NAILED THRU ROOF
9) PLAN SD2 REQUIRES ROOFS TO BE NAILED NOT STAPLED