Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T05CM06210
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/02/2006 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
11/01/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) #14 AND #12 GAUGE WIRES CANNOT BE ON SAME GROUND LUG IN SERVICE PANEL 2) REVERSE PITCH ON A/C CONDENSATE LINE-CLAMP LINE IN PROPER LOCATION 3) DISHWASHER DRAIN MUST LOOP TO WITHIN 2" OF FLOOD RIM OF SINK OR INSTALL AIR GAP DEVICE 4) ALL REPEAT ITEMS-NEXT FAILURE WILL REFEE |
|
10/27/2006 | BUILDING - FINAL | Denied | 1) LABEL ALL CIRCUITS IN ELECTRIC PANEL 2) WIRES OF DIFFERENT GAUGE CANNOT BE ON SAME GROUND LUG IN PANEL 3) REVERSE PITCH ON A/C CONDENSATE 4) CLAMP IN PERMANENT LOCATION 5) DISHWASHER DRAIN MUST LOOP TO WITHIN 2" OF SINK FLOOD RIM OR SUPPLY AIR GAP |