Permit: T05CM06210

Parcel: 141092240

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T05CM06210

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/02/2006 BUILDING - FINAL Approved IVRS - Inspection :*
11/01/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) #14 AND #12 GAUGE WIRES CANNOT BE ON SAME GROUND LUG IN SERVICE PANEL
2) REVERSE PITCH ON A/C CONDENSATE LINE-CLAMP LINE IN PROPER LOCATION
3) DISHWASHER DRAIN MUST LOOP TO WITHIN 2" OF FLOOD RIM OF SINK OR INSTALL AIR GAP DEVICE
4) ALL REPEAT ITEMS-NEXT FAILURE WILL REFEE
10/27/2006 BUILDING - FINAL Denied 1) LABEL ALL CIRCUITS IN ELECTRIC PANEL
2) WIRES OF DIFFERENT GAUGE CANNOT BE ON SAME GROUND LUG IN PANEL
3) REVERSE PITCH ON A/C CONDENSATE
4) CLAMP IN PERMANENT LOCATION
5) DISHWASHER DRAIN MUST LOOP TO WITHIN 2" OF SINK FLOOD RIM OR SUPPLY AIR GAP