Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM06200
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/20/2006 | FRAMING | Approved | IVRS - Inspection :* | |
09/19/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OUTLET BOXES CAN'T SHARE STUD BAY WHEN ON OPPOSING SIDES OF A FIREWALL-GARAGE X 2 2) REPLACE BLOWN FIREBLOCK IN MASTER 3) FIREBLOCK W. OF ENTRY 4) FIRESTOP CHASE E. OF ENTRY |
|
09/15/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ANTI-SIPHON VALVES REQUIRED AT HOSE BIBS 2) PROVIDE LARGER WASHER AT SPLIT BOTTOM PLATE IN GARAGE 3) TIGHTEN ALL RED HEADS 4) BANG PLATES ON ELECTRICAL 5) EXTERIOR SHEATHING ON ROMEX MUST ENTER OUTLET BOX 1/4" MINIMUM 6) RECALL ROOF NAILING AND COMPLY 7) STOPPED INSPECTION |