Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T05CM06200
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/11/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
06/13/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TRUSS LAYOUT AND BEARING POINTS ARE NOT PER APPROVED PLANS BUILD TO PLAN OR REVISE AS BUILT. 2) NEXT FAILURE WILL BE CHARGED A REFEE 3) STOPPED INSPECTION |
|
05/23/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TRUSS CLIPS NOT NAILED ONE SIDE 2) TRUSS DRAWINGS APPEAR TO HAVE BEEN MODIFIED WITHOUT APPROVAL-AGAIN. PROVIDE A COMPLETE SET OF CITY OF TUCSON APPROVED TRUSS DRAWINGS WITH EACH PAGE STAMPED BY CITY OF TUCSON. NO ZEROX COPIES 3) CHANNELS NOT NAILED PER 3/DT1 4) TRUSSES NOT CLIPPED PER 14/DT1 5) 6/DT1 REQUIRED AT 48" ON CENTER 6) ROOF NOT INSPECTED-STOPPED INSPECTION |