Permit: T05CM06194

Parcel: 141093210


Addresses:

6353 E RAVEN RUN LP


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T05CM06194

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
03/06/2006 ELECTRIC - RECONNECT Approved
02/22/2006 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*PROPERLY LABLE MAIN BREAKER
PROVIDE PROPER WORKING CLEARANCE IN FRONT OF ELEC. PEDESTAL
( THE GAS METER CANNOT BE IN THE 30" WIDTH x 36" DEPTH REQUIRED WORKING CLEARANCE