Permit: T05CM06173

Parcel: 141091760

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T05CM06173

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
07/27/2006 FRAMING Approved IVRS - Inspection :*
07/25/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS 3 AND 5 FROM 7/21/06 NOT DONE
07/21/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STUCCO LATHE NOT COMPLETE AT FRONT GABLE
2) 17/D1 NOT COMPLIED WITH AT GARAGE SHEARWALL 5
3) NAIL PROTECT WIRES WITHIN 1 1/4" OF PLATE/STUD SURFACES
4) NO DWV WATER TEST ABOVE 4 FEET MUST BE TO ROOF
5) BLOCK DUCT BOOTS ON 3 SIDES
6) FIRE STOP REQUIRES 2 LAYERS OF 1/2" OSB
7) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF PLATE/STUD SURFACES