Permit: T05CM06164

Parcel: 13109066A


Addresses:

5839 E 24TH ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
03/27/2008 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*
1) SUB PANEL INSPECTED
11/09/2007 ELECTRIC - TEMPORARY SERVICE Partial Approval IVRS - Inspection :*
11/06/2007 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TEMP SERVICE TO BE OUTSIDE BUILDING. INSTALL GFI RECEPT AT SERVICE ENTRANCE & REPLACE 125 AMP BREAKER WITH SINGLE POLE 20A
2. CONDUCTOR SIZE TO PANEL IN UNIT NOT PER PLAN. NOT SIZED PROPERLY FOR 125 AMP MAIN BREAKER
PLAN CALLS FOR PANELS TO BE MAIN BREAKER NOT MAIN LUG