Permit: T05CM06127

Parcel: 141091820

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T05CM06127

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
08/03/2006 FRAMING Approved IVRS - Inspection :*
08/01/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NAIL PROTECT WIRES WITHIN 1 1/4" OF PLATE/STUD SURFACE
2. FIRE STOP CHASE AT ENTRY
3. REMOVE WIRES FROM TRUSS GANG NAILS
4. GAS LINE NOT INSTALLED
07/20/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BANG PLATE ON ELECTRIC GARAGE SHEAR AND THROUGHOUT
2) H2.5'S MISSING NAILS THROUGHOUT
3) SEAL PENETRATION ON VAPOR BARRIER OVER TUB NORTH WALL
4) MOVE PEX AWAY FROM CAN LIGHTS AND WIRES
5) DRYER VENT BROKEN IN CEILING
6) MISSING STAPLES ON MESH AT FRONT PORCH TOP
7) NORTH SIDE GABLE NOT LATHED
8) NO WATER PRESSURE
9) NO DWV TEST