Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM06121
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/08/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/05/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEED BUSHINGS FOR #4 AND LARGER WIRE. 2. DON'T USE STRANDED UNDERGROUND NUT. 3. INSTALL 30 AMP. BREAKER FOR #10 WIRE. 4. COMPLETE ALL WIRING. 5. PROVIDE EARTH GROUND TO ALARM PANEL. 6. PAY RE-INSPECTION FEE PRIOR TO FINAL APPROVAL. 7. PROVIDE APPROVED PLAN FOR EMERGENCY LIGHTING. |
|
06/02/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* FINISH WIRING, 30 AMP. MAX FOR INSTA-HOT, EXIT SIGN IDENTIFY EQUIPMENT. CHECK EMERGENCY LIGHTING. |
|
06/01/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* CALL WHEN COMPLETE. |
|
05/24/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* WORK NOT COMPLETE |