Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2005 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
| 12/20/2005 | EXCAVATION/LAYOUT REBAR & ZON | Not ready for Inspection | IVRS - Inspection :* 1) CLAY SEWER NOT ALLOWED UNDER SLAB 2) SEE LAST INSPECTION |
|
| 12/15/2005 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BEDROOM WINDOW NOT PER CODE FOR EGRESS 2) CIRCUITS AT PANEL NOT IDENTIFIED 3) OUTSIDE OUTLET NOT GFCI 4) EXPOSE CORNER FOOTER 5) EXPOSE SEWER LINES 6) GFCI IN BATHROOM NOT POPPING 7) NEED SMOKE DETECTORS IN ALL BEDROOMS 8) KITCHEN MISSING GFCI'S 9) VENT WATER HEATER 10) TRV MUST TERMINATE 6" AF GRADE 11) WATER HEATER NOT LISTED FOR EXT. INSTALL 12) EXPOSE GAS LINE NEXT TO BATHROOM 13) LIGHT IN CLOSET TO CLOSE TO COMBUSTIBLES |