Permit: T05CM06085


Addresses:

6126 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Permit Number - T05CM06085

Inspection Description - PLUMBING - GAS PRESS TEST FNL

Inspection Status - Approved

Date Description Inspector Results Comments
07/13/2006 PLUMBING - GAS PRESS TEST FNL Approved IVRS - Inspection :*
14 PSI TEST FROM METER TO (1) FURNACE & (1) WATER HEATER ONLY OK
GAS CARD BY LAST INSPECTOR.
06/21/2006 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection :
See detailed listing on site.| 999*
USE PIPE SUPPORTS TO SECURE PIPING ON WALL
T&P TERMINATION HAS BEEN VANDALIZED.
24" ABOVE GRADE IS OK
3/4 TEE IS UNDERSIZED FOR 140,000 BTU AT 100+'
PROVIDE FULL SIZED TEE.
PROVIDE SHUT OFF VALVE AT BUILDING PER NOTE #9
ADD REPLACEMENT OF WH TO PERMIT. NEW GAS FLEX IS REQUIRED.