Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T05CM06085
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/13/2006 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* REVISED APPROVED PLAN ON SITE. |
|
03/21/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | WAITING ON REVISED CITY APPROVED PLAN | |
03/08/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR CANCELLED |
|
03/07/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* SEE NOTE #3 FROM 3/3/06 INSPECTION SEE NOTE #5 SAME SEE NOTE #6 SAME PIPE WRAPS OK BUILDING INTERIOR. |
|
03/03/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) WATER TEST PER RED LINE DRAWING ON SITE TO 5' PAST PARTITION WALL AT MISSION COUPLING OK PENDING APPROVED REVISED PLAN AT FUTURE DATE 2) HAVE 03005 AND 03057 SITE SEWER ADDED TO PERMIT CARD 3) PROVIDE WATER TEST ON BLDG DRAIN FROM ABOVE POINT OF COUPLING THRU TO CONNECTION TO EXISTING SEWER HCS WITH APPROVED COUPLINGS IN PLACE AT ALL CLEANOUTS AND CONNECTION POINTS 4) PROVIDE TRACER WIRE FOR ALL BURIED NON METALIC BLDG SEWER PIPING INSTALLED 5) PROVIDE VERIFICATION OF GRADE WITH CAMERA FOR PULLED POLY PIPE. COVER AT OWN RISK ONLY TO POINT OF COUPLING ABOVE 6) HAVE PIPE WRAP INSPECTION PRIOR TO CONCRETE POUR BACK 6) ALL DEMO WASTE AND VENT PIPING TO BE CAPPED AND INSPECTED WITH CORRECT PERM CAPS PRIOR TO COVERING |