Permit: T05CM06085


Addresses:

6126 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T05CM06085

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
07/13/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
REVISED APPROVED PLAN ON SITE.
03/21/2006 PLUMBING - ROUGH, SOIL Partial Approval WAITING ON REVISED CITY APPROVED PLAN
03/08/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELLED
03/07/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
SEE NOTE #3 FROM 3/3/06 INSPECTION
SEE NOTE #5 SAME
SEE NOTE #6 SAME
PIPE WRAPS OK BUILDING INTERIOR.
03/03/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) WATER TEST PER RED LINE DRAWING ON SITE TO 5' PAST PARTITION WALL AT MISSION COUPLING OK PENDING APPROVED REVISED PLAN AT FUTURE DATE
2) HAVE 03005 AND 03057 SITE SEWER ADDED TO PERMIT CARD
3) PROVIDE WATER TEST ON BLDG DRAIN FROM ABOVE POINT OF COUPLING THRU TO CONNECTION TO EXISTING SEWER HCS WITH APPROVED COUPLINGS IN PLACE AT ALL CLEANOUTS AND CONNECTION POINTS
4) PROVIDE TRACER WIRE FOR ALL BURIED NON METALIC BLDG SEWER PIPING INSTALLED
5) PROVIDE VERIFICATION OF GRADE WITH CAMERA FOR PULLED POLY PIPE. COVER AT OWN RISK ONLY TO POINT OF COUPLING ABOVE
6) HAVE PIPE WRAP INSPECTION PRIOR TO CONCRETE POUR BACK
6) ALL DEMO WASTE AND VENT PIPING TO BE CAPPED AND INSPECTED WITH CORRECT PERM CAPS PRIOR TO COVERING