Permit: T05CM06085
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/20/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH ITEM #1 PREVIOUS INSPECTIONS |
|
| 07/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FINISH PREVIOUS ITEMS 1, 3 , 4 |
|
| 07/03/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 2. LIGHT IN CLOSET TO MAINTAIN CLEARANCES FROM SHELVING PER 410.8 3. WHERE IS REVISED PLAN WITH WILDAN STAMP? ALSO REVISED PANEL SCHEDULE. 4. WHERE IS "F" FIXTURE IF DELETED PLEASE REVISE FIXTURE SCHEDULE AND ENERGY LOAD CALC'S. 5. GROUND OUTLET BOXES ALSO USE LISTED APPROVED CONNECTORS FOR MC CABLE 6. USE BREAKERS LISTED BY MANUFACTURER 7. SEPARATE GROUNDED AND GROUNDING CONDUCTORS AT SUB-PANEL. ALSO PROVIDE A GROUNDING PATH. |