Permit: T05CM06085


Addresses:

6126 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM06085

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/13/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
05/15/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. SUPPORT VDV CABLING AS PER 725.6
2. PLEASE VERIFY BOXES ARE LISTED FOR USE WITH M/C CABLE.
3. WE HAVE BOX OVERFILL.
4. SUPPORT M/C WITHIN 12" OF BOXES.
5. SUPPORT CONDUITS ABOVE PANEL AND ON HORIZONTAL RUNS AS PER CODE.
6. JUNCTION BOX TO BE ACCESSIBLE.
7. PANEL P-2 IS NEW PLANS CALL IT EXISTING.
8. NO MORE THAN 360 DEGREES IN A CONDUIT RUN ALLOWED.
9. DO TREATMENT ROOM FALL UNDER 517.13?