Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL |
|
| 04/09/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT CONDENSATE DRAIN LINES AND PAINT WITH LATEX PAINT 2) MARK UNIT DATA PLATES 3) PROVIDE MINIMUM R8 DUCT LINER IN EXPOSED SUPPLY DUCT ON ROOF |