Permit: T05CM06080

Parcel: 107120630

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/25/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
NEED RANGE INSTALLED (ALL UNITS)
04/12/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
UNIT #1 ONLY
CORRECTIONS NOT COMPLETE FROM PREVIOUS INSPECTION ALSO, NEED TO PROVIDE LADDER TO ROOF
WILL NEED TO PAY REINSPECTION FEE
04/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) INSPECTION FOR UNIT 1 ONLY: INSTALL ALL LIGHT BULBS, HOOD TO
2) INSTALL CORRECT WATTAGE BULBS
3) SMOKE DETECTORS NEED ARC FAULT PROTECTION NEC 210.12 B
4) ALARM RECEPTACLE/BOX LOOSE
5) DISHWASHER NOT TO BE ON KITCHEN COUNTER CKT NEC 210.52 B 2 FINISH DISHWASHER/DISP WIRING
6) MARK RTU DATA PLATES
7) KITCHEN COUNTER RECEPTACLES TO BE 20 AMP CKT/NO OTHER LOADS NEC 210.52
8) CORRECTLY IDENTIFY PANEL DIRECTORY NEC 408.4