Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* NEED RANGE INSTALLED (ALL UNITS) |
|
| 04/12/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* UNIT #1 ONLY CORRECTIONS NOT COMPLETE FROM PREVIOUS INSPECTION ALSO, NEED TO PROVIDE LADDER TO ROOF WILL NEED TO PAY REINSPECTION FEE |
|
| 04/09/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) INSPECTION FOR UNIT 1 ONLY: INSTALL ALL LIGHT BULBS, HOOD TO 2) INSTALL CORRECT WATTAGE BULBS 3) SMOKE DETECTORS NEED ARC FAULT PROTECTION NEC 210.12 B 4) ALARM RECEPTACLE/BOX LOOSE 5) DISHWASHER NOT TO BE ON KITCHEN COUNTER CKT NEC 210.52 B 2 FINISH DISHWASHER/DISP WIRING 6) MARK RTU DATA PLATES 7) KITCHEN COUNTER RECEPTACLES TO BE 20 AMP CKT/NO OTHER LOADS NEC 210.52 8) CORRECTLY IDENTIFY PANEL DIRECTORY NEC 408.4 |