Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/20/2007 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 03/07/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL ADDRESS AND UNIT NUMBERS ON SERVICE 2. SEAL ROOF FLASHING 3. SEAL OPENING COMPLETELY IN TOP OF SERVICE 4. SECURE MAST TO STRUCTURE 5. SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE AND TERMINATE ON LUG PROVIDED ON NEUTRAL BAR. 6. TIGHTEN SERVICE CONDUCTOR LUGS WITH PROPER SIZE ALLEN WRENCH. |