Permit: T05CM06080

Parcel: 107120630

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/25/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/08/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SMOKE DETECTORS 36"
2. ROMEX CONNECTORS INTO SUB-PANELS
3. ROOFTOP SERVICE RECEPTACLE
4. CHECK BOX BRACE ON STEEL STUDS.

OK COVER AFTER CORRECTIONS
12/06/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
CORRECTIONS NOT MADE -- FINISH ALL CORRECTIONS BEFORE YOU CALL IN. ALSO, EXTERIOR RECEPTACLE NOT ALLOWED ON KITCHEN CKT -- NEC 210.52 (B2) AND SMOKE DETECTORS NEED 36" MINIMUM SEPARATION FROM HVAC VENTS C VENTS NOT IN FIRST INSPECTION.

CHARLIE 349-5029 IF YOU WOULD LIKE TO GO OVER INSTALLATION.
11/29/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SECURE ALL BOXES -- NEC 314.23A
2. USE PROPER CRIMP TOOL ON CRIMP SLEEVES - NEC 110.3
3. SCREWS/NAILS NOT ALLOWED INSIDE BOXES -
NEC 314.23 B1
4. NEED REAR EXTERIOR RECEPTACLE - NEC 210.52 E
5. USE PROPER ROMEX CONNECTORS FOR ROMEX ENTERING SUB-PANELS.
6. PROVIDE ADDITIONAL BRACE FOR BOXES ON STEEL STUDS NEC 314.23
7. HAVE OVERFILLED BOXES - NEC 314.16
8. EQUIPMENT ABOVE CEILING IN BATHROOM?
9. WHERE IS ATTIC ACCESS? MAKE SURE WIRING IS PROTECTED -- NEC 334.23
10. ROMEX TO SIT BACK IN WALL -- NEC 300.5
2ND UNIT NOT READY