Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/08/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SMOKE DETECTORS 36" 2. ROMEX CONNECTORS INTO SUB-PANELS 3. ROOFTOP SERVICE RECEPTACLE 4. CHECK BOX BRACE ON STEEL STUDS. OK COVER AFTER CORRECTIONS |
|
| 12/06/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* CORRECTIONS NOT MADE -- FINISH ALL CORRECTIONS BEFORE YOU CALL IN. ALSO, EXTERIOR RECEPTACLE NOT ALLOWED ON KITCHEN CKT -- NEC 210.52 (B2) AND SMOKE DETECTORS NEED 36" MINIMUM SEPARATION FROM HVAC VENTS C VENTS NOT IN FIRST INSPECTION. CHARLIE 349-5029 IF YOU WOULD LIKE TO GO OVER INSTALLATION. |
|
| 11/29/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SECURE ALL BOXES -- NEC 314.23A 2. USE PROPER CRIMP TOOL ON CRIMP SLEEVES - NEC 110.3 3. SCREWS/NAILS NOT ALLOWED INSIDE BOXES - NEC 314.23 B1 4. NEED REAR EXTERIOR RECEPTACLE - NEC 210.52 E 5. USE PROPER ROMEX CONNECTORS FOR ROMEX ENTERING SUB-PANELS. 6. PROVIDE ADDITIONAL BRACE FOR BOXES ON STEEL STUDS NEC 314.23 7. HAVE OVERFILLED BOXES - NEC 314.16 8. EQUIPMENT ABOVE CEILING IN BATHROOM? 9. WHERE IS ATTIC ACCESS? MAKE SURE WIRING IS PROTECTED -- NEC 334.23 10. ROMEX TO SIT BACK IN WALL -- NEC 300.5 2ND UNIT NOT READY |