Permit: T05CM06065

Parcel: 11615088L

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
06/01/2006 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
05/22/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. CHECKED FIRE DAMPER CANS, CORRIDOR GRID APPL.
04/17/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/31/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SMOKE WALL NEED TO EXTEND 5/8 X RATED ROCK MUST BE CONTINUED TO POINT OF SMOKE DAMPER TO CONTINUE THE INTEGRITY OF RATED WALL.
JOB PROGRESSING
JOINTS SEALED - OK TO START WRAPPING DUCT.