Permit: T05CM06065

Parcel: 11615088L

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
06/20/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
05/04/2006 PLUMBING - INTERMEDIATE Partial Approval
04/27/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PLUMBING IN ROOMS 372, 373, 374 OK TO COVER
2. MEDICAL GAS LABELING OK
04/24/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/21/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/21/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. MED GAS ALONG CORRIDOR 349 LABELING OK
2. PLUMBING ROOM #307 OK TO COVER.
3. ROOM 311 & 318 OK TO COVER
ROOM 371 OK TO COVER AFTER INSULATION
04/17/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PRIVATE ROOMS ALONG CORRIDOR 349
DWV & COPPER ABOVE CEILING OK
INTERMEDIATE APPROVED PREVIOUSLY.
2. SEMI PRIVATE ROOMS ALONG CORRIDOR 350 EXCEPT 307
OK TO COVER WALLS DWV & COPPER
OK TO COVER CEILING DWV & COPPER
3. MED GAS ONGOING
REMEMBER -- BRANCHES OFF OF MAINS TO BE TAKEN OFF ABOVE MAIN.
04/13/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
# ROOMS
#300, #309, #313 OK TO COVER
MED GAS UNDER TEST
04/07/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ROOMS #304, 306, 354 AND 335 MED GAS ON GOING
2) OK TO COVER THESE ROOMS-PLUMBING
04/05/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. MED GAS INSTALL GOING OK CHECKED PAPER WORK
2. TRAP ARM CORRECTED
04/03/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/30/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. MED GAS START UP OR CALL AGAIN IN A COUPLE OF DAYS.